人工引雷中金属氧化物避雷器响应特性

Response Characteristics of Metal-oxide Arrester Subjected to Rocket-triggered Lightning

  • 摘要: 为明确金属氧化物避雷器(metal-oxide arrester,MOA)在极端暂态冲击下的响应特性,依托中国气象局雷电野外科学试验基地,于2024年8月12日对500 kV线路MOA阀片开展了人工引雷雷电流直接注入试验,研究其动态响应与失效过程。结果表明:人工引雷先驱放电前,雷暴云电场驱动负电荷沿金属线下行,使得MOA两端背景电压逐渐降至-16.6 kV;先驱放电一旦启动,电场分布的改变导致该电压向零刻线偏移。电压脉冲表明先驱放电对应下降沿仅1.2 μs的充电过程,随后经等效10 MΩ和200 pF的阻容电路缓慢放电,对应持续数毫秒的上升沿。先驱放电阶段MOA尚未导通,持续时间1.6 μs、下降沿0.7 μs的电流脉冲反映了电荷在大地与电容下极板间的迁移过程。初始连续电流强度与持续时间均远超先驱放电,其电荷经阻容放电持续通过MOA,迫使MOA从高阻态转入热致导通,端电压突变至直流参考电压,引发热崩溃并炸裂。回击阶段MOA内部已贯通为碳化通道,该通道在回击电流通过时呈现13~21.4 Ω的低阻特性。

     

    Abstract: Metal-oxide arrester (MOA) is a critical overvoltage protection device in power transmission systems; however, its transient response and failure mechanisms under extreme lightning current injection condition remain poorly understood. Lightning current from rocket-triggered lightning is directly injected into a varistor block extracted from a 500 kV transmission-line MOA at Field Experiment Base on Lightning Sciences, China Meteorological Administration, and the current waveform through the MOA and the voltage waveform across its terminals are recorded. Prior to the precursor discharge, the thundercloud’s negative charge region drives negative charges downward along the metal wire, gradually decreasing the MOA terminal background voltage to -16.6 kV. During the precursor discharge, positive charges release from the wire tip shift the background voltage back toward zero. Each precursor pulse corresponds to a rapid charging process with a falling-edge duration of only 1.2 μs, followed by a slow discharge through an equivalent resister-capacitor (R-C) circuit (10 MΩ, 200 pF), which produces a voltage rising edge lasting several milliseconds. In the precursor discharge stage, the MOA remains non-conductive, and the measured current pulse, with a duration of 1.6 μs and a falling edge of 0.7 μs, reflects charge migration between ground and the lower plate of the equivalent capacitance. The initial continuous current exhibits an intensity and a duration far exceeding those of the precursor discharge. The charge carried by this current continuously flows through the MOA via the R-C discharge path, forcing the MOA to transition from its high-impedance state into an abnormal conduction state. Upon this transition, the terminal voltage abruptly jumps to the direct current reference voltage, thereby triggering thermal runaway and causing explosive varistor fracture. By the subsequent return stroke stage, the interior of the MOA has already been penetrated, forming a carbonized channel that exhibits a low resistance of 13-21.4 Ω as the return-stroke current passes through. It is concluded that the MOA failure under triggered lightning is initiated during the initial continuous current phase, long before the peak of the return stroke. R-C discharge behavior dominates the pre-conduction dynamics, and the forced transition to a conductive state is a critical cause of the eventual thermal destruction. These findings provide experimental evidence of the transient response of MOA under direct lightning strikes and further clarify their ultimate withstand capability under extreme lightning conditions.

     

/

返回文章
返回