高塔多重雷击电流的直接测量与物理特征

Direct Measurement and Physical Characteristics of Multi-stroke Lightning Currents in Tall Towers

  • 摘要: 利用自主研制的高塔雷电流直接测量装置,于2024—2025年在四川攀枝花输电铁塔与湖北武汉长江航运大厦开展观测,共记录到3次自然负极性多重雷击,包含18次回击,丰富了我国多重雷击电流基础数据。统计分析上述回击电流波形的物理特征参数及参数间关联关系表明:单次多重雷击最多包含9次回击,最大平均峰值电流、平均波头最大上升速率、转移电荷总量及能量积分总量分别为-17.47 kA、2.13 kA·μs-1、-42.75 C和5.68×105 A2·s;相邻回击时间间隔平均为75.60 ms,后续回击与首次回击峰值比中值为0.33;雷击能量释放受峰值电流平方律支配,波头最大上升速率与峰值电流呈线性关系,回击间隔与幅值比例呈显著负相关;与国内外观测数据相比,实测波形峰值偏小、波头偏缓,但持续时间长、电荷与能量总量大。上述多重雷击物理特征可为输电铁塔及城市高层建筑的差异化防雷设计与评估提供数据支撑。

     

    Abstract: To enrich fundamental data of multiple-stroke lightning currents in China, a direct measurement device for tall towers is developed. It features a measurement range of ±400 kA, a frequency bandwidth of 10 Hz to 2.5 MHz, a sampling rate of 5×106 s-1, and a maximum recording duration if 2 s. Within 5-80 kA range, the peak-current measurement error is less than 1.86%, verifying the monitoring capability of the device.
    Observations are conducted at transmission towers in Panzhihua (30-m) and Yangtze River Shipping Mansion (336 m) in Wuhan from 2024 to 2025. 3 natural negative multiple-stroke flashes, comprising 18 return strokes, are recorded. Physical characteristic parameters and their correlations are statistically analyzed and compared with previous domestic and international observation results.
    Statistical results indicate Panzhihua transmission tower strike consists of 9 return strokes, with the average peak current of -17.47 kA, maximum rising rate of 2.13 kA·μs-1, total charge transfer of -42.75 C, and total impulse energy of 5.68×105 A2·s. The first strike observed at Wuhan Yangtze River Shipping Mansion contains 4 return strokes, with corresponding values of -6.75 kA, 1.05 kA·μs-1, -5.92 C, and 3.52×104 A2·s, respectively. The second strike observed in Wuhan Yangtze River Shipping Masion includes 5 return strokes, with these values of -2.16 kA, 0.50 kA·μs-1, -6.42 C, and 5.05×104 A2·s. The average interval between successive return strokes is 75.60 ms, and the median ratio of subsequent to first return stroke peaks is approximately 0.33.
    It reveals that the energy release of multiple lightning strikes on tall towers follows a square-law dependence on current, which can be expressed by the fitting relationship J=0.5|Ipeak|1.63. A linear empirical formula is established between the maximum rate of rise and the peak current: Sm=0.11|Ipeak|. Furthermore, a notable negative correlation is observed between the return stroke interval (△trs) and the amplitude ratio (ramp). Compared with domestic and international data, the lightning current waveforms recorded in this observation exhibit a distinct “short and wide” profile, characterized by lower peaks and slower wavefronts but longer durations, which lead to larger total charge transfers and impulse energies. These physical characteristics of multiple-stroke lightning provide empirical data support for the differentiated lightning protection design and risk assessment of transmission towers and urban high-rise buildings.

     

/