Direct Measurement and Physical Characteristics of Multi-stroke Lightning Currents in Tall Towers
-
Abstract
To enrich fundamental data of multiple-stroke lightning currents in China, a direct measurement device for tall towers is developed. It features a measurement range of ±400 kA, a frequency bandwidth of 10 Hz to 2.5 MHz, a sampling rate of 5×106 s-1, and a maximum recording duration if 2 s. Within 5-80 kA range, the peak-current measurement error is less than 1.86%, verifying the monitoring capability of the device.
Observations are conducted at transmission towers in Panzhihua (30-m) and Yangtze River Shipping Mansion (336 m) in Wuhan from 2024 to 2025. 3 natural negative multiple-stroke flashes, comprising 18 return strokes, are recorded. Physical characteristic parameters and their correlations are statistically analyzed and compared with previous domestic and international observation results.
Statistical results indicate Panzhihua transmission tower strike consists of 9 return strokes, with the average peak current of -17.47 kA, maximum rising rate of 2.13 kA·μs-1, total charge transfer of -42.75 C, and total impulse energy of 5.68×105 A2·s. The first strike observed at Wuhan Yangtze River Shipping Mansion contains 4 return strokes, with corresponding values of -6.75 kA, 1.05 kA·μs-1, -5.92 C, and 3.52×104 A2·s, respectively. The second strike observed in Wuhan Yangtze River Shipping Masion includes 5 return strokes, with these values of -2.16 kA, 0.50 kA·μs-1, -6.42 C, and 5.05×104 A2·s. The average interval between successive return strokes is 75.60 ms, and the median ratio of subsequent to first return stroke peaks is approximately 0.33.
It reveals that the energy release of multiple lightning strikes on tall towers follows a square-law dependence on current, which can be expressed by the fitting relationship J=0.5|Ipeak|1.63. A linear empirical formula is established between the maximum rate of rise and the peak current: Sm=0.11|Ipeak|. Furthermore, a notable negative correlation is observed between the return stroke interval (△trs) and the amplitude ratio (ramp). Compared with domestic and international data, the lightning current waveforms recorded in this observation exhibit a distinct “short and wide” profile, characterized by lower peaks and slower wavefronts but longer durations, which lead to larger total charge transfers and impulse energies. These physical characteristics of multiple-stroke lightning provide empirical data support for the differentiated lightning protection design and risk assessment of transmission towers and urban high-rise buildings.
-
-